            High Temperature Fireproof Control Cable

            耐高(gao)溫防火控製(zhi)電(dian)纜(lan)1.jpg
            • 耐高(gao)溫(wen)防火(huo)控製電纜1.jpg
            High temperature fire-resistant control cables are suitable for signal detection in high temperature…

            Description:

            I. Overview of Cables:

            High temperature fire-resistant control cables are suitable for signal detection in high temperature environment with AC rated voltage of 300/500 or less. Especially suitable for fire protection and security system protection circuit control and power transmission line.

            II. Implementation criteria

            GB9330-88

            3. Use characteristics:

            1. AC rated voltage: U0/U 450/750V;

            2. Maximum operating temperature: flame retardant PVC insulation and sheath 70 ~105 ~C;

            Fluoroplastics insulation and sheath at 200 C and 260 C;

            The insulation temperature of crosslinked polyethylene is 90 C.

            Low smoke halogen-free flame retardant polyolefin 70 C;

            Low smoke halogen-free flame retardant crosslinked polyolefins at 90 ~125 ~C.

            3. Minimum ambient temperature: flame retardant polyvinyl chloride sheath fixed laying - 40 C, non-fixed laying - 15 C;

            Fluoroplastics insulation and sheath fixed laying - 60 C, non-fixed laying - 20 C;

            4. Fire resistance

            According to IEC 331, flame temperature 750 C, combustion time 3h, cooling time 12h, additional rated voltage, additional 3A current

            According to GB12666.6-A, flame temperature 950-1000 C, combustion time 90min, additional rated voltage 3A current

            According to GB12666.6-B, flame temperature 750-800 C, combustion time 90 min, additional rated voltage 3A current

            5. Installation and laying temperature of cable should not be lower than 0 and fluoroplastic sheathed cable should not be lower than - 25 C.

            6. The recommended permissible bending radius for laying: non-armoured cables should be no less than 6 times of cable outer diameter, armoured cables should be no less than 12 times of cable outer diameter, and fluoroplastic insulated and sheathed cables should be no less than 8 times of cable outer diameter.

            4. Basic Types and Names of High Temperature Fire-proof Control Cables

            Model name

            NH-KVV Flame Retardant PVC Insulated and Sheathed Fire Resistant Control Cables

            NH-KVVP Flame Retardant PVC Insulated and Sheathed Copper Wire Braided Shielded Fire Resistant Control Cable

            NH-KVVP2 Flame Retardant PVC Insulated and Sheathed Copper Strip Enveloped Shielded Fire Resistant Control Cable

            NH-KFF Fluoroplastic Insulated and Sheathed Fire Resistant Control Cable

            NH-KFFP Fluoroplastic Insulated and Sheathed Copper Wire Braided Shielded Fire Resistant Control Cable

            NH-KFFP2 Fluoroplastic Insulated and Sheathed Copper Ribbon Shielded Fire Resistant Control Cable

            NH-KVDVD Low Smoke Low Halogen Flame Retardant PVC Insulated and Sheathed Fire Resistant Control Cable

            NH-KVDVDP Low Smoke Low Halogen Flame Retardant PVC Insulated and Sheathed Copper Wire Braided Shielded Fire Resistant Control Cable

            NH-KVDVDP2 Low Smoke Low Halogen Flame Retardant PVC Insulated and Sheathed Copper Strip Enveloped Shielded Fire Resistant Control Cable

            NH-KYDYD Low Smoke Halogen-Free Flame Retardant Polyolefin Insulated and Sheathed Fire-Resistant Control Cable

            NH-KYDYDP Low Smoke Halogen-Free Flame Retardant Polyolefin Insulation and Sheathed Copper Wire Braided Shielded Fire-Resistant Control Cable

            NH-KYDYDP2 Low Smoke Halogen-Free Flame Retardant Polyolefin Insulation and Sheathed Copper Strip Enveloped Shielded Fire Resistant Control Cable

            NH-KYJV XLPE Insulated Flame Retardant PVC Sheathed Fire Resistant Control Cable

            NH-KYJVP Crosslinked Polyethylene Insulated Flame Retardant PVC Sheathed Copper Wire Braided Shielded Fire Resistant Control Cable

            NH-KYJVP2 Cross-linked Polyethylene Insulated Flame Retardant PVC Sheathed Copper Strip Enveloped Shielded Fire Resistant Control Cable

            Note: After the armored cable type, add 22. The shielding type of soft structure cable can be in the form of P2, P3, etc.

            5. Code Name and Meaning

            Item Code Description

            Refractory Characteristics NH Refractory Cables A or B

            Series code K control cable

            Insulation material V. PVC, flame retardant PVC

            Y polyethylene

            YD Low Smoke Halogen-Free Polyolefin (YDJ Low Smoke Halogen-Free Crosslinked Polyolefin)

            YJ Crosslinked Polyethylene

            F. Fluoroplastics at 200 and 260 degrees Celsius

            Sheath Material V. PVC, Flame Retardant PVC

            F. Fluoroplastics at 200 and 260 degrees Celsius

            YD Low Smoke Halogen-Free Polyolefins

            Shielding Material P Copper Wire Braided Shielding

            P2 Copper Strip Envelope Shielding

            P3 Aluminum-plastic Wrapping Shielding

            Armored Material 22 Steel Belt Armored PVC Sheath

            32. Steel wire armoured polyvinyl chloride sheath

            Conductor structure A. Single conductor

            B 7 stranded conductors

            R. Multiple stranded conductors

            Main Technical Indicators

            Performance Items Unit Technical Indicators

            Conductor DC Resistance <DC_/KM Cross Section mm2 0.5 0.75 1.5 2.5

            Category A 36.0 24.5 18.1 12.1 7.41

            Class R 39.0 26.0 19.5 13.3 7.98

            Test voltage

            2.5KV/5min

            Insulation Resistance M_/KM 1000

            Fire resistance

            GB12666.6A or B

            Flame retardant properties

            GB12666.5A or B


            Delivery Length of High Temperature Fireproof Control Cable:

            Cables are generally no less than 100 meters, allowing short-term delivery of more than 50 meters, not more than 10% of the total length of delivery; measurement error is less than 50. If there is a special request, the supplier and the demander can negotiate separately.

            Specification for cable type:

            Example 1 Five-core 1.0mm 2A type conductor high temperature fire-resistant cable is expressed as NHFF 5 x 1.0 (A)

            Example 2: 1.0mm 2B type conductor steel tape armoured shielded high temperature fire-resistant cable with five core section is expressed as NHFP1F22 5 *1.0(B)